AC MACHINES-1 (66761) Theory
7. Realize the construction and Principle of operation of three phase transformer.
7.5. Describe Scott or T-T connection.
SCOTT-T TRANSFORMER CONNECTION
Definition: The Scott-T Connection is the method of connecting two single phase transformer to perform the 3-phase to 2-phase conversion and vice-versa. The two transformers are connected electrically but not magnetically.One of the transformers is called the main transformer, and the other is called the auxiliary or teaser transformer.
PHASOR DIAGRAM OF SCOTT CONNECTION TRANSFORMER
The line voltages of the 3-phase system VAB, VBC, and VCA which are balanced are shown in the figure below. The same voltage is shown as a closed equilateral triangle.The figure below shows the primary windings of the main and the teaser transformer.
THE VOLTAGE BETWEEN A AND D IS
The teaser transformer has the primary voltage rating that is √3/2 or 0.866 of the voltage ratings of the main transformer. Voltage VAD is applied to the primary of the teaser transformer and therefore the secondary of the voltage V2t of the teaser transformer will lead the secondary terminal voltage V2m of the main transformer by 90º as shown in the figure below.
Then,
POSITION OF NEUTRAL POINT N
The voltage across AN = VAN = phase voltage = Vl/√3.
Since the voltage across the portion AD.
the voltage across the portion ND
The same voltage turn in portion AN, ND and AD are shown by the equations,
The equation above shows that the neutral point N divides the primary of the teaser transformer in ratio.
AN : ND = 2 : 1
APPLICATIONS OF SCOTT CONNECTION
The following are the applications of the Scott-T connection.
- The Scott-T connection is used in an electric furnace installation where it is desired to operate two single-phase together and draw the balanced load from the three-phase supply.
- It is used to supply the single phase loads such as electric train which are so scheduled as to keep the load on the three phase system as nearly as possible.
- The Scott-T connection is used to link a 3-phase system with a two–phase system with the flow of power in either direction.
The Scott-T connection permits conversions of a 3-phase system to a two-phase system and vice versa. But since 2-phase generators are not available, the converters from two phases to three phases are not used in practice.